Watertightness is defined as the non-entry of water through areas not foreseen or desirable although on occasions it is better not to stop water coming in but rather facilitate its collection and later removal.
In the same way, in locations heated with mobile butane gas heaters, in kitchens and in damp locations, measures should be taken to collect condensation water.
The UNE 85-220-86 instruction sets out some recommendations for the selection of the degree of watertightness as a function of the disposition and the V class required by wind, applicable in areas with similar precipitation levels to those of the wettest areas of Catalonia.
Table 8
Window class according to degree of watertightness
Height H between windows Window faces Class of window required by wind
VI V2 V3 *
H <= 3m
3m<H<=5m
Exteriors
Interiors
Exteriors
-
EI
E2
EI
E2
E2
EI
E2
E3
E2
E3
E4
NOTES
1.-The symbol * means special window more resistant than V3.
2.-The symbol - means that watertightness is not a relevant factor in the choice of carpentry.
3.-E is the degree of window watertightness based on testing according to the UNE 85-229 norm, Method 1, by which there is no entry of water which might come into contact with parts of the structure not foreseen as getting wet, with a continuous flow of a (b+2) litres per minute (with a and b in metres) and a pressure of:
Degree of watertightness EI E2 E3 E4
Test pressure (Pa) >=50 >=150 >=300 >=500
Category Normal Improved Reinforced Exceptional